Parameter

Special Method of Aggregation

Voltage Under Deviation

where n = the number of 10/12-cycle r.m.s. values for underdeviation during the aggregation interval and Urms−under,i is the ith 10/12-cycle r.m.s. value

Voltage Over Deviation

where n = the number of 10/12-cycle r.m.s. values for overdeviation during the aggregation interval and Urms−over,i is the ith 10/12-cycle r.m.s. value

Flicker

10-min Interval: Aggregated on the basis of the probability distribution function for the instantaneous flicker values 

2- hour Interval: Aggregated on the basis of the last 12 values of short term flicker values according to the following method

Instantaneous Flicker

Aggregated by taking the average of the measured values in 10 min

 Power (Instantaneous)

Aggregated by taking the Average of the measured values in the aggregation intervals (150/180 Cycles, 10-min) 

Power Demand (Quantity and Value)

Aggregated by taking the Average of the measured values in the demand interval which is input by the user.

Energy 

Aggregated by taking the Average of the measured values in 10 min (reset each 10 min) (no accumulation)

Accumulated Energy

Aggregated by accumulating each 1 min without reset


Created with the Personal Edition of HelpNDoc: Make Documentation Review a Breeze with HelpNDoc's Advanced Project Analyzer