Line to Neutral connection (L-N)
|
Earth line MUST be connected if you install Line to Neutral. |
|
(L-N) connection is used in SINGLE/THREE PHASE CONNECTION. |
|
Hardware MUST be configured with Line to Neutral. if it’s reversed, causes FIRE RISK. |
- Before UPS: a jumper between 4 and 6
- After UPS: a jumper between 4 and 6 and a jumper between 7 and 9
- You will find that powering terminals are divided to three parts
- The first part (Before UPS Connectors) consists of 8 connectors:
- Connector number 4 and connector number 6 must be shorted together using fork-terminals short
- Connector number 1 is connected to the first phase of the Main cable
- Connector number 3 is connected is connected to the neutral of the Main cable
- Connector number 5 and Connector number 8 are Not Connected
- The second part is a couple of connectors used for connecting earth of the 3-wires cable
- The second part (After UPS Connectors) consists of 9 connectors:
- Connector number 4 and connector number 6 must be shorted together using fork terminals short
- Connector number 7 and connector number 9 must be shorted together using fork terminals short
- Connector number 1 is connected to the first phase of the UPS cable
- Connector number 3 is connected is connected to the neutral of the UPS cable
- Connector number 5 and Connector number 8 are Not Connected
After connecting power Rosetta Line to Neutral, you need to connect a short between AC_IN socket and PH_N socket as shown in figures here.