A pump hunts around its setpoint. A fan trips at one particular speed. A conveyor draws inconsistent current. A motor runs hotter than its identical neighbour. The fastest fix is to replace the drive or the motor — and when the real cause is the supply or the process, the new one fails the same way.
This guide covers two related investigations: unstable processes driven by variable frequency drives (VFDs), and motors that show electrical stress. Both start from the same principle: separate the supply, the drive and the mechanical load before blaming any one of them.
Part 1: unstable VFD-driven processes
The question to answer
Is the instability linked to the supply, the drive output, or the mechanical load?
Why a normal meter gets this wrong
On the supply side of a drive, voltage and current are close to sinusoidal at 50 or 60 Hz. On the motor side they are not: the drive outputs pulse-width-modulated (PWM) voltage at a frequency that changes with speed. A conventional RMS meter, or one that assumes a fixed 50/60 Hz fundamental, produces numbers on the motor side that may not mean what they appear to mean.
The measurement plan
- Treat the drive supply and the motor side as separate measurement domains, where the configuration supports it, each with the processing mode intended for it — grid mode for the input, VFD mode for the output.
- Record the process context: speed or frequency setpoint, process demand, and pressure or flow from compatible sensors or external logs.
- Capture both stable operation and the transitions that trigger the complaint.
Reading the evidence
- Compare stable operating regions first, then the transitions.
- Does the current change follow the process demand? Then the drive is probably responding correctly to a process problem.
- Is the disturbance already present at the drive input? Then look upstream — see tracing voltage sags.
- Does the same pattern repeat at one particular speed? That points towards mechanical resonance or a control-loop setting rather than the supply.
Don’t over-read PWM measurements. Fast-edge overshoot, cable reflection peaks, bearing currents and accurate dv/dt cannot be inferred from a general sampling rate. They need suitably rated probes, sufficient bandwidth and a validated analysis. VFD analysis on Inspector depends on the approved configuration and probes — confirm what is enabled for your installation.
Acting on the evidence
Assign the next step to the right specialist — upstream supply, drive settings, control-loop tuning or the mechanical process — and verify any change against both the electrical trend and the process response. Keep the grid-side and drive-output views separate, so that supply-quality indicators are never applied to a variable-frequency waveform.
Part 2: motor electrical stress
The question to answer
Does the evidence point to supply imbalance, operating duty, or a problem with the motor itself? A single high current reading answers none of these.
Why voltage unbalance matters
A small voltage unbalance between phases produces a disproportionately larger current unbalance in an induction motor, and that extra current becomes heat. A motor that runs hot on one feeder and cool on another may be perfectly healthy — and simply connected to an unbalanced supply. The effect should always be evaluated against the motor manufacturer’s guidance and the applicable operating limits.
The measurement plan
- Record the nameplate, connection, driven equipment, operating speed and load state.
- Capture all three phases of voltage and current at a defined point, comparing like-for-like operation.
- Add temperature and process context where available.
- Record the method used to calculate unbalance, and distinguish measured speed from any model-based estimate.
Inspector measures negative- and zero-sequence unbalance alongside RMS voltage and current, power and power factor on each channel, and the Motor Measure Unit adds non-invasive current monitoring on up to three motors per module.
Reading the evidence
- Is voltage unbalance accompanied by disproportionate current unbalance? Suspect the supply or a connection first.
- Does loading rise with process demand? The motor may simply be working harder.
- Does the complaint appear only during a particular duty — frequent starts, a specific product, a hot afternoon?
An electrical trend alone does not establish winding insulation condition or shaft output power.
Acting on the evidence
- Check supply and connection hypotheses first, where the evidence supports them.
- Then review mechanical loading, cooling and duty with the responsible teams.
- Use a targeted offline motor test or additional sensing when online measurements cannot answer the question.
- Confirm the improvement under equivalent load and ambient conditions.
Estimates are not measurements. Motor electrical analysis is configuration-dependent. Do not treat estimated speed, torque, loading or efficiency as independently measured quantities.
What to measure to show value
- nuisance trips and unstable operating periods,
- repeated overload conditions and phase imbalance,
- start frequency,
- recurrence of the original complaint,
- energy per unit of process output, where reliable flow or production data exist.
The goal is a stable operating envelope and a traceable reason for every adjustment.